4-Pole
Generator Voltage
Load
Speed
Frequency
120V(110) 240V (220)
Applied
(rpm) (Hertz)
Plants Plants
None 1830
62 122 240
(1530)
(52)
(112)
(224)
Half
1800
60
120 240
(1500) (50)
(110) (220)
Full 1755 59
110 220
(1455)
(49)
(100) (200)
The output voltage should be checked periodically
to
ensure proper operation
of
the generating plant and
the appliances it supplies.
If an AC voltmeter
or
ampmeter is not installed
to
monitor voltage and load, check it with a portable meter
and amp-probe.
Preventive
Maintenance
(Generator)
Maintenance on the generator is minimal.
1.
Keep the generator clean,
dry
and well-ventilated.
2.
Make sure all connections are clean and tight and that cables carrying AC voltage are properly supported
and protected against chafing.
3.
The rear armature bearing is lubricated and sealed; therefore,
no
maintenance is required.
If
the bearing
becomes rough
or
noisy, replace it.
Generator
Troubleshooting
A complete and illustrated text on troubleshooting the BC series of generators is furnished in the Technical
Manual which is available through your local dealer.